Sign In | Join Free | My fazendomedia.com |
|
Brand Name : GDZX
Model Number : ZX2677E
Certification : ISO9001
Place of Origin : China
MOQ : 1Set
Price : US $919.00-1879.00/SET
Payment Terms : L/C,T/T,Western Union,MoneyGram,D/A,D/P,WeChat,Paypal
Supply Ability : 1200sets/year
Delivery Time : 7-20 work days
Packaging Details : Packing wooden case or carton
Product name : Digital high-voltage Insulation tester
Base conditions : 23°C±5°C,below 75%rh
Rated voltage(V) : 250;500;1000;2500;5000V;10KV;
Test Voltage(V) : rated voltage*(1±10%)
Insulation Resistance Range(GΩ) : 0.01MΩ~2000GΩ
Voltage Range : DC:0~1000V; AC: 0~750V
Power Supply : 12V rechargeable battery;
Data Storage : 500 groups, "FULL" symbol indicates that storage is full;
Instrument weight : 2750g(including battery);
Working Temperature and Humidity : -10℃~+50℃,<85%RH;
ZX2677E Digital insulation resistance meter also known as megohmmeter, high voltage insulation resistance tester, etc., for the insulation resistance test. The instrument has a large LCD screen gray backlit display, data storage, data access, alarm, automatic shutdown and other functions. At the same time, it also has the function of measuring AC voltage absorption ratio and polarization index of DC voltage. The machine is beautiful and upscale, has a wide range, high resolution, convenient operation, easy to carry, accurate, reliable, stable performance, strong anti-interference ability. Moreover, it has a shockproof, dustproof, moisture-proof structure and is a commonly used and indispensable instrument for telecommunications, electricity, meteorology, computer rooms, oil fields, electromechanical installation and maintenance, and industrial enterprises that use electricity as industrial power or energy.
Features
1. The instrument has a large LCD screen gray backlit display, data storage, data access, alarm, automatic shutdown and other functions.
2. The function of measuring AC voltage absorption ratio and polarization index of DC voltage.
3. Digital insulation resistance meter consists of medium and large scale integrated circuits.
4. The output power of the watch is large, and the output voltage level is a lot (with 6 voltage levels).
5. Rated insulation test voltage range 250V ~ 10kV, insulation resistance measurement range 0.01MΩ ~ 2000GΩ.
6. DC voltage measurement range 0 ~ 1000V, AC voltage measurement range 0 ~ 750V.
Technical Indicators
Function | Insulation resistance test, voltage test | |
Base conditions | 23°C±5°C,below 75%rh | |
Rated voltage(V) | 250;500;1000;2500;5000V;10KV | |
Test Voltage(V) | rated voltage×(1±10%) | |
Insulation Resistance Range(GΩ) | 0.01MΩ~2000GΩ | Resolution:0.01MΩ |
DC Voltage Range | 0~1000V | Resolution:0.1V |
AC Voltage Range | 0~750V | Resolution:0.1V |
Output short-circuit Current | ≥5mA(10KV) | |
Absorption Ratio and Polarization Index Measurement | Have | |
Power Supply | 12V rechargeable battery | |
Backlight | Controllable gray screen backlight, suitable for use in dim places | |
Dispaly mode | 4-bit large LCD display, gray screen backlight | |
LCD display size | 108mm×65mm | |
Instrument size | L/W/H:277.2mm×227.5mm×153mm | |
USB interface | With USB interface, software monitoring, storage data can be uploaded to the computer, save the print | |
Communication Line | USB communication line 1PC | |
Test Line | High voltage rob red 3meter, high voltage test line black 1.5meter, green 1.5meter | |
Data Storage | 500 groups, "FULL" symbol indicates that storage is full | |
Data Review | Data review function: "MR" symbol display | |
Overflow Display | Exceed measurement range overflow function: “OL ” symbol display | |
Alarm Function | Alarm when the measured value smaller than the alarm setting value | |
Power Consumption | Standby: 30mA Max(backlight off), turn on backlight: 42mA Max, measure:300mA Max(backlight off) | |
Instrument weight | 2750g(including battery) | |
Battery voltage | When the battery voltage is low, low battery symbol “ battery ”will display | |
Automatic shut-down | automatic shutdown after 15 minutes boot | |
Insulation Resistance | ≥50MΩ(between Measuring line and housing) | |
Pressure Resistance | AC3kV/50Hz 1min | |
Working Temperature and Humidity | -10℃~+50℃<85%RH | |
Storage Temperature and Humidity | -15℃~+55℃<90%RH | |
Suitable for Safety Regulations | IEC61010-1,IEC1010-2-31,IEC61557-1,5,IEC60529(IP54) pollution grade 2,CAT Ⅲ 300V |
![]() |
ZX2677E Portable 10KV Digital Insulation Resistance Tester Shockproof With LCD Display Images |